Sizing an inverter when motors start, not just run

Continuous rating versus surge capability, and the load types that decide which governs.

The engineering question

The inverter trips every time the compressor starts. Is it too small, or is the surge the real constraint?

Worked example

The figures below were produced by running the Inverter Sizing Calculator with the same inputs — during the build, from its authoritative engine.

Results
Continuous rating required 4375 W
Surge rating required 14000 W
Assessment Size the inverter for ≥ 4375 W continuous and ≥ 14000 W surge (motors start at 3–5× running load for a few seconds).
  1. Continuous rating is the largest simultaneous load plus a design margin.
  2. Surge rating is that load multiplied by the starting factor for the load type.
  3. The inverter must satisfy whichever requirement is larger.

Sanity check

Compressor and motor starting can be three to five times running load, but only for a few seconds. A soft starter may be cheaper than a larger inverter.