Inverter Sizing Calculator

Continuous and surge inverter rating from the largest load, a load-type surge factor and a design margin.

Add this calculator to the Construction Workflow

Geometry-based calculation.Continuous sizing with a margin plus a surge requirement derived from a load-type factor. It does not model efficiency curves, parallel units or grid-tie export limits.

Workspace

Continue where you left off

Saved calculations in this browser can be reopened with their inputs intact.

Open Workspace

What this calculator does

An inverter that is too small clips the array output; one that is too large wastes money. This calculator sizes the continuous rating from your load with a margin, then checks whether your worst starting load fits within the surge capability you are likely to need.

How to use it

  1. Enter the largest simultaneous continuous load, in watts.
  2. Select the surge factor: 1 for resistive loads, 3 for motors, 4 for compressors and 2 for a mixed load.
  3. Set the margin, 25 % being a common allowance for future loads and inverter derating at high temperature.
  4. Size the inverter for whichever is larger — the continuous requirement or the surge requirement.

Governing formula

Governing Formula
P_cont = P_load × (1 + m) ; P_surge = P_load × f_surge

Where:

  • m = Design margin [–]
  • f_surge = Surge factor for the load type [–]

Worked example — 3,500 W of loads with motors

The figures below were produced by running this page's own engine with the example inputs (Largest continuous load (W), Largest starting load, Design margin (%)). If the calculator returns something different for the same numbers, that is a bug, not a rounding difference.

Expected results for the worked example
Continuous rating required4375 W
Surge rating required7000 W
AssessmentSize the inverter for ≥ 4375 W continuous and ≥ 7000 W surge (motors start at 3–5× running load for a few seconds).
  1. Continuous rating with a 25 % margin is 4,375 W.
  2. A surge factor of 2 requires 7,000 W of surge capability.
  3. Select the smallest inverter meeting both — for this load, around 4,500 W continuous with at least 7 kW surge.

Assumptions & limitations

Engineering calculation. Continuous sizing with a margin plus a surge requirement derived from a load-type factor. It does not model efficiency curves, parallel units or grid-tie export limits.

  • Surge capability is quoted for a few seconds only; large motor starts that take longer need a soft starter or a larger unit.
  • Inverter efficiency varies with load, so a heavily oversized unit runs less efficiently at low load.
  • Does not consider battery voltage window, grid-tie export limitation or parallel inverter configurations.

This tool supports professional engineering work; it does not replace a sealed design. Confirm every result against the applicable standard and a licensed engineer before it is built.

References & standards

  • IEC 62109 — safety of inverter converters for photovoltaic systems.
  • Manufacturer datasheets for surge duration and continuous rating.
Engineering Disclaimer & Verification Notice

This calculator provides preliminary engineering estimates for informational and planning purposes. Actual reverse osmosis / engineering system performance depends on site conditions, feed-water chemistry, membrane characteristics, operating pressure, temperature, recovery limits, fouling/scaling potential, and system design. Verify results using project-specific data, manufacturer projections, and applicable engineering standards before final design or operation.