Battery bank size and how long it should last
Converting daily demand and autonomy into stored energy, and why depth of discharge changes the answer so much.
The engineering question
How many ampere-hours of battery does an off-grid system need, and what does the autonomy figure really promise?
Worked example
The figures below were produced by running the Battery Bank Sizing Calculator with the same inputs — during the build, from its authoritative engine.
| Required bank energy | 18500 Wh |
|---|---|
| Required bank capacity | 385.4167 Ah |
| Series strings | 4 no |
| Parallel strings | 4 no |
| Assessment | 18.5 kWh bank ≈ 385 Ah at 48 V → 4S × 4P of 100 Ah 12 V batteries. Size cables and OCPD for the bank current. |
- Stored energy is daily demand times autonomy, divided by usable depth of discharge.
- Capacity in ampere-hours is that energy divided by the system voltage.
- Series batteries set the voltage; parallel strings set the capacity.
Sanity check
Lead-acid at 50 % depth of discharge needs roughly twice the lithium bank for the same autonomy. If the two give the same answer, the depth of discharge was not applied.
Tools for this problem
These are the EngiMetric calculators that compute the numbers in this topic. Each one shows its formula, its units and its limits rather than returning a bare result.
Engineering review required
This topic supports professional engineering work; it does not replace a sealed design. The result depends on site data, the governing standard and engineering judgement, and should be confirmed by a competent engineer before it is built.
References & standards
- IEC 62619 — industrial lithium cells and batteries
- NREL — off-grid system sizing
Related problems
How many solar panels a load actually needs
From appliance energy to module count, with the derating that stops an array from under-delivering.
Also: Electrical
Sizing an inverter when motors start, not just run
Continuous rating versus surge capability, and the load types that decide which governs.
Also: Electrical