Select heat rejection and cooling equipment
Size cooling units and heat rejection from the calculated duty, and expose the water and ambient assumptions behind the selection.
- Advanced
- 14 stages
- 16 min
- Mission-critical electrical and thermal systems
After this stage you can
- Size cooling units against duty, reserve and topology.
- Quantify post-failure cooling capacity and the load it can still serve.
- State when water consumption applies and when it does not.
The engineering
The cooling plant is sized from the required duty including reserve and the selected unit rating. The topology check requires a spare unit for N+1 or two full paths for 2N. Post-failure capacity is reported separately from installed capacity.
Chiller performance is never invented. The learner supplies design COP at a stated ambient and a COP sensitivity. The energy stage uses those values hour by hour. If the selection cannot support an honest result, the model reports missing inputs instead of a hidden default.
Water is calculated only for heat rejection that actually evaporates water. The estimate uses latent heat, cycles of concentration and drift. It is a screening water balance, not a permit application. Air-cooled and dry heat rejection report no evaporative demand in this boundary.
EngiMetric / AI data-center workbench
One project, computed from rack to report
Loading the saved project state...
Preview screen. Inputs are saved in this browser only. Climate, grid, water and cost values are illustrative. Failed checks stay visible; a clean summary is not a stamped design and no Tier rating is claimed.
Your deliverable for this stage
A cooling equipment schedule and a heat-rejection concept with its water boundary.
Stage assumptions, limits and sources
Assumptions
- Chiller COP is a user-supplied design value, adjusted by the stated ambient sensitivity.
- Cooling units share duty equally.
- Evaporative make-up is estimated from latent heat, cycles and drift.
Constraints
- No vendor performance curve, chiller selection or water permit is produced.
Limitations
- No condenser approach, fouling, refrigerant, noise or water-treatment design.
- No part-load chiller sequencing or thermal storage.
Review status
- Needs engineering review
- Professional review is required before publication or use as a design basis.
Sources
- Uptime Institute - Tier Standard overviewengineering org
- ASHRAE - Data Center Guidance and Datacom Seriesengineering org
- Open Compute Project - Data Center Facility projectengineering org
- NVIDIA - DGX SuperPOD reference architectureofficial docs
- U.S. Department of Energy - Data centers and serversgovernment
Stage progress is stored in this browser only. The explanation and every limit on this page remain readable with JavaScript disabled; the calculators need it to run.
Stage kind: Calculation / Journey: ai-data-center / Stage: cooling-equipment