When the ground can absorb the water, and when it cannot
Sizing infiltration storage and soakaways, and recognising the soils that will not drain.
The engineering question
Surface water has to go somewhere. Which soils can take it, and how do you size the trench that stores it?
Worked example
The figures below were produced by running the Soakaway Calculator with the same inputs — during the build, from its authoritative engine.
| Storage required | 3.5625 m³ |
|---|---|
| Required base area | 2.9688 m² |
| Soakage rate | 50 mm/h |
| Square pit side (square option) | 1.723 m |
| Assessment | Need ≈ 3.6 m³ storage; a 1.2 m-deep pit with ≈ 1.7 m × 1.7 m base (≈ 3 m²) suits the 50.0 mm/h soakage rate from the 20 s/mm test. Backfill with washed aggregate and geotextile. |
- The percolation test time inverts to a soakage rate in mm per hour.
- Storage is the design rainfall depth times the area and the runoff coefficient.
- Base area is that storage divided by the depth, giving the pit footprint.
Sanity check
Clay soils give very long percolation times. If the test result is slow, a soakaway is the wrong answer regardless of the storage calculation.
Tools for this problem
These are the EngiMetric calculators that compute the numbers in this topic. Each one shows its formula, its units and its limits rather than returning a bare result.
- Soakaway Calculator Soakaway storage and base area from a percolation test result, the drainage area and the design storm.
- Infiltration Trench Calculator Length and drain time of an infiltration trench from the stored runoff volume, void ratio and soil infiltration rate.
- Bioswale Calculator Trapezoidal bioswale geometry, storage volume, media void storage and drawdown time for a given infiltration rate.
Engineering review required
This topic supports professional engineering work; it does not replace a sealed design. The result depends on site data, the governing standard and engineering judgement, and should be confirmed by a competent engineer before it is built.
References & standards
- BS EN 752-4 — soakaways and small developments
- Local authority soakaway test requirements
Related problems
How much stormwater storage a site actually needs
Comparing peak inflow against the permitted discharge and turning the difference into a storage volume.
Also: Civil & Structural
How much greywater a building actually produces, and can you use it
Quantifying the reusable fraction of household wastewater and the storage it needs.
Also: Plumbing & Fire