How much stormwater storage a site actually needs

Comparing peak inflow against the permitted discharge and turning the difference into a storage volume.

The engineering question

The site cannot discharge as fast as rain arrives. How much storage has to be provided, and how big does the pond need to be?

Worked example

The figures below were produced by running the Detention Basin Calculator with the same inputs — during the build, from its authoritative engine.

Results
Peak inflow 0.1877 m³/s
Required storage 157.77 m³
Pond footprint at that depth 131.475 m²
Assessment Peak inflow 0.19 m³/s vs 0.10 m³/s release → ≈ 158 m³ storage; at 1.2 m depth the pond footprint is ≈ 131 m².
  1. Peak inflow follows the Modified Rational Method: Q = 2.78·C·i·A.
  2. Storage is the excess above the permitted release over the storm duration.
  3. Pond footprint is that volume divided by the design depth.

Sanity check

If the permitted release exceeds the peak inflow, no storage is required and the calculation will return zero.