EngiMetric Arena / Spot the Error

Review this voltage-drop check: the phase factor is wrong

  • Spot the Error
  • Electrical
  • intermediate
Competency Quantitative reasoning primary Evidence interpretation supporting

What you should take away: Use the correct voltage-drop factor for a balanced three-phase circuit and distinguish a failed check from a failed design.

The situation

What is happening

A 400 V, 100 A balanced three-phase feeder runs 150 m to a packaged plant. The conductor resistance is 0.727 ohm/km and the project allows 5 % voltage drop. The reviewer used a round-trip factor of 2 and rejected the design at 5.45 %. Review the calculation.

Given

Scenario values with units
QuantityValueUnitNote
System voltage 400 V Line-to-line, balanced three-phase.
Design current 100 A Full-load current.
One-way run 150 m Cable route length.
Conductor resistance 0.727 ohm/km 25 mm2 copper at the calculator reference temperature.
Allowable drop 5 % Project limit.

Assumptions this challenge makes

  • The load is balanced across the three phases.
  • Reactance is neglected, as in the voltage-drop engine used here.
  • The conductor resistance is taken at the calculator reference temperature.

Your call

Your answer

Which review finding is defensible?

What this challenge does not establish

  • Reactance is neglected. On large conductors or high-current feeders, reactance can be a significant part of the drop.
  • The conductor resistance is a table value at a reference temperature, not the operating temperature of this installation.
  • Ampacity, short-circuit withstand, protective-device coordination and derating are not assessed here.
  • The load is assumed balanced; an unbalanced three-phase load needs a different calculation.