EngiMetric Arena / Engineering Trade-off

Choose a cable size that satisfies drop and ampacity

  • Engineering Trade-off
  • Electrical
  • advanced
Competency Constraints and trade-offs primary Quantitative reasoning supporting

What you should take away: Evaluate a cable choice against two independent electrical criteria and a physical termination limit, accepting that more than one standard size is defensible.

The situation

What is happening

A 400 V, 100 A balanced three-phase feeder runs 180 m. The project allows 4 % voltage drop, and the switchgear terminals accept conductors up to 95 mm2. Specify a standard conductor size that satisfies voltage drop, ampacity and the terminal limit.

Given

Scenario values with units
QuantityValueUnitNote
System voltage 400 V Line-to-line, balanced three-phase.
Design current 100 A Full-load current.
One-way run 180 m Cable route length.
Allowable drop 4 % Project limit.
Terminal limit 95 mm2 Largest conductor the switchgear accepts.

Assumptions this challenge makes

  • The load is balanced and the conductor resistance is taken from the calculator table.
  • Reactance is neglected, as in the voltage-drop engine.
  • Ampacity is the tabulated free-air value; installation method and grouping are not applied.

Limits this decision must satisfy

Project limits the submitted value must satisfy
Limit Requirement If it is breached
Voltage drop not more than 4 % Above 4 % the load voltage is outside the project limit and the feeder must be enlarged or shortened.
Ampacity not less than 100 A Below the design current the conductor would overheat, regardless of how small its voltage drop is.
Terminal size not more than 95 mm2 Above the terminal limit the cable cannot be landed on the supplied switchgear without a transition.

Any standard size that holds every stated limit is defensible. Larger sizes buy margin but cost more and may not fit the terminals.

Your call

Your answer

Any standard size that holds every stated limit is defensible. Larger sizes buy margin but cost more and may not fit the terminals.

What this challenge does not establish

  • Ampacity is the tabulated free-air value; installation method, ambient temperature, grouping and derating are not applied.
  • Reactance, skin effect and harmonics are neglected.
  • The terminal limit is a project assumption, not a manufacturer’s verified data sheet.
  • Protective-device coordination, short-circuit withstand and earth-fault loop impedance are separate checks.