Sizing a cable for both current and voltage drop
Two independent constraints that must both be satisfied, and recognising which one actually chose the size.
The engineering question
Current-carrying capacity and voltage drop are separate limits. What do you do when they give different answers?
Worked example
The figures below were produced by running the Wire Sizing Calculator with the same inputs — during the build, from its authoritative engine.
| Recommended conductor size | 10 mm² |
|---|---|
| Resulting voltage drop | 2.2915 % |
| Ampacity of that size | 55 A |
| Minimum size by ampacity alone | 4 mm² |
| Maximum permitted resistance | 2.3958 Ω/km |
| Assessment | Minimum 10 mm² (55 A ampacity) holds drop to 2.3%. |
- The largest acceptable resistance follows from the drop limit and the route length.
- The smallest size with enough ampacity follows from the current alone.
- The chosen size is the larger of the two — and derating factors may push it further.
Sanity check
If the recommended size equals the ampacity-only size, the run is short enough that current governs and voltage drop is irrelevant.
Tools for this problem
These are the EngiMetric calculators that compute the numbers in this topic. Each one shows its formula, its units and its limits rather than returning a bare result.
Engineering review required
This topic supports professional engineering work; it does not replace a sealed design. The result depends on site data, the governing standard and engineering judgement, and should be confirmed by a competent engineer before it is built.
References & standards
- IEC 60364-5-52 — ampacity and voltage drop
- NEC 310.16 — allowable ampacities
Related problems
Why the voltage at the end of the cable is lower than at the supply
Calculating voltage drop over the run, and why the cable size that satisfies current may not satisfy voltage.
Why a conduit cannot be filled completely, and how full is too full
Conduit fill percentages by conductor count, the reason they exist, and choosing the next conduit when the first does not fit.
Also: Construction & QS
Choosing a transformer: why standard sizes matter more than the load
Applying diversity and growth to connected load, then selecting the next standard rating and understanding the utilisation.