Working out the static pressure a fan has to overcome

Velocity, friction factor and pressure drop per 100 ft, and what that means for the fan duty to specify.

The engineering question

The fan selection needs a static pressure. Where does the number come from before the fan is chosen?

Worked example

The figures below were produced by running the Duct Friction & Pressure Drop Calculator with the same inputs — during the build, from its authoritative engine.

Results
Velocity 1432 fpm
Friction factor 0.0173 –
Pressure drop per 100 ft 5.3275 in.w.g.
Total pressure drop 5.3275 in.w.g.
Reynolds number 201845
Basis Swamee–Jain friction coefficient for galvanized round duct (0.0003 ft roughness). Flexible duct needs a roughness ~0.003 ft and 1.25× diameter allowance for the equivalent length note.
  1. Area from the diameter gives the velocity.
  2. Reynolds number and friction factor follow from roughness and diameter.
  3. Pressure drop per 100 ft scales with the real route length; fittings are added separately.

Sanity check

Friction factor should fall as diameter rises. A friction factor that increases with duct size indicates an error.

Tools for this problem

These are the EngiMetric calculators that compute the numbers in this topic. Each one shows its formula, its units and its limits rather than returning a bare result.

References & standards

  • ASHRAE Handbook — duct design and fitting losses
  • SMACNA — engineering manual

Related problems

Mechanical & Fluids Choose between alternatives

Finding the duty point instead of guessing a pump size

Reading a pump curve as a system curve, and matching the two to find where the system will actually operate.

  • Type Selection guide
  • Tools 4 linked
  • Review Needs engineering judgement