Duct Friction & Pressure Drop Calculator

Calculate round duct velocity, Reynolds number, friction factor and pressure drop per 100 ft before selecting a fan.

Add this calculator to the Construction Workflow

Geometry-based calculation.Evaluates the friction factor with the Swamee–Jain approximation and applies the Darcy–Weisbach relationship for standard air. Fitting and fitting losses are excluded.

Workspace

Continue where you left off

Saved calculations in this browser can be reopened with their inputs intact.

Open Workspace

What this calculator does

Every fan has to overcome duct friction, and the loss grows steeply with diameter, so size matters enormously. This calculator gives the velocity, Reynolds number, friction factor and pressure drop per 100 ft for a round duct, which is the first check before selecting a fan.

How to use it

  1. Enter the airflow and the nominal duct diameter.
  2. Enter the total run length so the total pressure drop can be reported.
  3. Use 0.0003 ft for galvanised steel duct and about 0.003 ft for flexible duct.
  4. Keep the friction factor in a sensible band — below 0.02 for small ducts, below 0.015 for large.

Governing formula

Governing Formula
f = 0.25 / [log₁₀(ε/3.7D + 5.74/Re⁰·⁹)]² ; ΔP = f · (L/D) · ρV²/2

Where:

  • ε = Absolute surface roughness [ft]
  • D = Internal diameter [ft]
  • Re = Reynolds number of the air stream [–]

Worked example — 2,000 CFM through a 16 in galvanised duct

The figures below were produced by running this page's own engine with the example inputs (Airflow (CFM), Duct diameter (in), Total length (ft), Surface roughness (ft)). If the calculator returns something different for the same numbers, that is a bug, not a rounding difference.

Expected results for the worked example
Velocity1432 fpm
Friction factor0.02 –
Pressure drop per 100 ft5.33 in.w.g.
Total pressure drop5.33 in.w.g.
Reynolds number201845
BasisSwamee–Jain friction coefficient for galvanized round duct (0.0003 ft roughness). Flexible duct needs a roughness ~0.003 ft and 1.25× diameter allowance for the equivalent length note.
  1. The flow area of a 16 in duct is 1.40 ft², giving about 1,432 fpm.
  2. At that velocity the friction factor lands near 0.0155, so expect roughly 0.10 in.w.g. per 100 ft.
  3. Multiply by the real route length and add fittings before sizing the fan.

Assumptions & limitations

Engineering calculation. Evaluates the friction factor with the Swamee–Jain approximation and applies the Darcy–Weisbach relationship for standard air. Fitting and fitting losses are excluded.

  • Round ducts only; rectangular ducts need the hydraulic diameter and a different friction reference.
  • Fittings, elbows and take-offs are excluded — add their equivalent length or loss coefficient separately.
  • Standard air only; at altitude the density and kinematic viscosity both change.

This tool supports professional engineering work; it does not replace a sealed design. Confirm every result against the applicable standard and a licensed engineer before it is built.

References & standards

  • ASHRAE Handbook — Fundamentals, duct design and fitting loss data.
  • SMACNA — Engineering Manual for duct design.
Engineering Disclaimer & Verification Notice

This calculator provides preliminary engineering estimates for informational and planning purposes. Actual reverse osmosis / engineering system performance depends on site conditions, feed-water chemistry, membrane characteristics, operating pressure, temperature, recovery limits, fouling/scaling potential, and system design. Verify results using project-specific data, manufacturer projections, and applicable engineering standards before final design or operation.