Does a lower A1-A3 carbon total prove a lower whole-life carbon?

  • Interpret & Validate
  • Construction & QS
  • intermediate
Competency Evidence interpretation primary Quantitative reasoning supporting

What you should take away: Distinguish a cradle-to-gate material comparison from a whole-life carbon assessment and state the scope boundary explicitly.

The situation

What is happening

A screening compares a concrete frame using 100 000 kg of concrete at 0.12 kg CO2e/kg with a steel frame using 10 000 kg of steel at 1.5 kg CO2e/kg. Both factors are labelled A1-A3 only. The concrete option totals 12 t CO2e and the steel option 15 t CO2e. A colleague concludes that the concrete frame has lower whole-life carbon. Choose the defensible interpretation.

Given

Scenario values with units
QuantityValueUnitNote
Concrete quantity 100 000 kg Concrete frame material.
Concrete factor 0.12 kg CO2e/kg A1-A3 only.
Steel quantity 10 000 kg Steel frame material.
Steel factor 1.5 kg CO2e/kg A1-A3 only.
Concrete total 12 t CO2e 100 000 x 0.12 / 1 000.
Steel total 15 t CO2e 10 000 x 1.5 / 1 000.

Assumptions this challenge makes

  • Both emission factors are user-supplied and carry an A1-A3 scope label.
  • The quantities are compared on the same functional basis.
  • Transport, construction, maintenance and end-of-life are not included in either factor.

Your call

Your answer

Which interpretation is defensible?

What this challenge does not establish

  • The factors are user-supplied and are not verified by the engine.
  • The quantities are not converted to a common functional unit beyond the stated comparison.
  • The calculation does not include transport, construction, maintenance, replacement or end-of-life.
  • A 25 % difference in A1-A3 does not establish a 25 % difference in whole-life carbon.