Water Engineering Verified Calculator

Septic Tank Sizing Calculator

Septic tank volume and standard size from residents, daily flow, retention time and the sediment storage allowance.

Geometry-based calculation.Sizes the septic tank from daily flow, retention time and a sediment-storage factor. The leach field is not sized — it depends on soil percolation.

Workspace

Continue where you left off

Saved calculations in this browser can be reopened with their inputs intact.

Open Workspace

What this calculator does

A septic tank is a holding and settling vessel, so its size follows from how much water goes in and how long it stays. This calculator converts residents into a daily flow, applies the retention time your code requires, adds the sludge allowance and selects the next standard size.

How to use it

  1. Enter the number of residents and the daily flow per person — 130 to 180 litres is the usual range.
  2. Set the retention time required by the local code, commonly 48 hours for a single dwelling.
  3. The sediment factor of 1.3 allows for the third compartment where solids accumulate.
  4. The leach field must be sized separately from a percolation test.

Governing formula

Governing Formula
V = (n × q) × (t/24) × factor

Where:

  • n = Number of residents [–]
  • q = Flow per person [L/day]
  • t = Retention time [h]

Worked example — Five residents at 150 L/day

The figures below were produced by running this page's own engine with the example inputs (Residents, Flow per person (L/day), Required retention time (h), Sediment storage factor (–)). If the calculator returns something different for the same numbers, that is a bug, not a rounding difference.

Expected results for the worked example
Required tank volume1.95 m³
Recommended standard size2 m³
Daily flow0.75 m³/day
AssessmentAt 150 L/p/d the tank needs ≈ 2.0 m³ → specify a 2 m³ tank. Check the treatment/soil-percolation requirement for the leach field.
  1. Daily flow is 5 × 150 = 750 L, or 0.75 m³/day.
  2. Two days of retention gives 1.5 m³, and the sediment factor raises it to about 1.95 m³.
  3. The next standard size is 2.0 m³.

Assumptions & limitations

Engineering calculation. Sizes the septic tank from daily flow, retention time and a sediment-storage factor. The leach field is not sized — it depends on soil percolation.

  • Tank sizing only — the drain field area depends on soil percolation, which this tool does not assess.
  • Local codes set minimum tank volumes that may exceed the calculated figure for small installations.
  • Assumes no commercial or industrial inflow.

This tool supports professional engineering work; it does not replace a sealed design. Confirm every result against the applicable standard and a licensed engineer before it is built.

References & standards

  • ASCE 24 — septic tank and leaching field design.
  • Local building codes — minimum septic tank capacity requirements.
  • EPA — onsite sewage treatment systems guidance.
Engineering Disclaimer & Verification Notice

This calculator provides preliminary engineering estimates for informational and planning purposes. Actual reverse osmosis / engineering system performance depends on site conditions, feed-water chemistry, membrane characteristics, operating pressure, temperature, recovery limits, fouling/scaling potential, and system design. Verify results using project-specific data, manufacturer projections, and applicable engineering standards before final design or operation.