Estimating water supply demand and the service pipe that carries it

Water supply fixture units converted to a probable peak demand, and the service size that follows.

The engineering question

How much flow does a building actually need at peak, when no fixture ever runs at full flow?

Worked example

The figures below were produced by running the Water Supply Fixture Unit Calculator with the same inputs — during the build, from its authoritative engine.

Results
Estimated peak demand 31.646 GPM
Total supply load 61.2 WSFU
Typical service size 1.5 in
Assessment Estimated peak demand ≈ 31.6 GPM for 61.2 WSFU (Hunter flush-tank curve) → starting service size ≈ 1.5" (verify against municipal pressure and the required fixture pressure).
  1. A bathroom group counts 3.6 units; other fixtures carry their own value.
  2. Add to a total, then interpolate the probable peak demand from the standard curve.
  3. That peak demand, not the sum of rated flows, is what sizes the service.

Sanity check

Peak demand grows far more slowly than the fixture count. A linear result means the fixture units have been multiplied by their rated flow.

Tools for this problem

These are the EngiMetric calculators that compute the numbers in this topic. Each one shows its formula, its units and its limits rather than returning a bare result.

References & standards

  • IPC 2018 Appendix E — supply fixture units and demand
  • Hunter — Methods of Estimating Loads in Plumbing Systems